FDS221-R Alarm sounder red

Email
Part no.: A5Q00004117
Loud alarming in case of fire alarm, clearly recognizable as danger signal. Loop driven

Application
Only applicable with addressable detector base FDB221 or FDB222.
For recess supply line.
For surface supply line with FDB221 until cable 6 mm in diameter, otherwise use base attachment
FDB291.
Along escape routes, corridors, staircases and is mounted on the wall or on the ceiling.


Function
Loud alarming in case of fire alarm, clearly recognizable as danger signal.
Synchronized of acoustic signals with all other alarm sounder devices and sounder bases in the same
detector line (C-NET).

Communication protocol  C-NET
 Operating voltage 12... 33 VDC 
 Operating current quiescent condition  250 μA
 Operating current ton activated  3.5 mA
 Ext. alarm indicator  2
 Connection terminals  according to the detector base
Number of sounds  11; 2 activation levels, 3 sound intensities
 Sound intensity  80... 99 dBA
 Operating temperature  -25... +70 °C
Storage temperature  -30... +75 °C
Humidity  ≤95 % rel.
 Color  red, ~RAL 3000, white, ~RAL 9010
 Protection category EN60529/IEC529 with
– Base FDB221 or FDB222
– Base attachment FDB291
– Base FDB221 and sealing element FDBZ295
– Base attachment wet FDB293
mounting on the wall with cable feed from bottom
–> IP43, otherwise IP40
IP44
IP54 
 System compatibility C-NET  FS720
Standards  EN54-3, EN54-17
Dimensions  Ø100 x 43 mm
Approvals   VdS G204073, LPCB request
   
Technical Details Table
A6V10203095
Technical Manual

 

008109
Data Sheet