FDL241-9 Linear smoke detector

Email
Part no.: A5Q00003941
Large storerooms and production workshops. Areas with complex roof structures or historically valuable
ceilings. Covered courtyards. Atrium-type buildings. Reception halls.

Application
Large storerooms and production workshops. Areas with complex roof structures or historically valuable
ceilings. Covered courtyards. Atrium-type buildings. Reception halls.
Can be used as an addressable or collective, conventional device.


Function
The detector consists of a light emitter and a light receiver. The light emitter emits a bundled infrared
ray, which is scattered back by the prism-shaped reflector to the light emitter. The receiver converts the
received infrared signal in an electric signal, which is evaluated by the microprocessor-controlled electronics.
Smoke penetrating the measuring section attenuates the infrared signal. When the signal reaches predefined
measuring values, the detector transmits the corresponding danger level to the control unit.
Distance measurement for the recognition of foreign matters. The built-in alarm indicator signals the
alarm status locally.
Max. Detection distance 5 – 100m.

Technical Details Table
007017
Data Sheet

 

007016
Technical Details

 

Communication protocol

C-NET, collective, conventional

Operating voltage addressable / collective, conventional

12... 33 VDC / 18... 28 VDC

Operating current addressable, collective, conventional

1.5 mA

Ext. alarm indicator

1

 

 

Operating temperature

-25... +60 °C

Storage temperature

-30... +75 °C

Humidity

white, ~RAL 9010

Color

white, ~RAL 9010

Protection category EN60529/IEC529

IP65

System compatibility collective, conventional

CZ10, BC10, FC10, XC10, CS11, FC700A,
FC330A, SIGMASYS, BMS, SM80/88/D100
Standards EN54-12, EN54-17

System compatibilityC-NET

FS720

Standards

 EN54-12, EN54-17

Dimensions

135 x 135 x 115 mm

Approvals

VdS G204063,

LPCB 126ag/01