FDCIO222 4 way Input/output module

Email
Part no.: A5Q00002369
For the connection of 4 independent, potential-free make or break contacts for the acknowledgement of
technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the
decentralized control of fire doors, ventilation, air conditioning, etc.
Addressable applicable.

Application
For the connection of 4 independent, potential-free make or break contacts for the acknowledgement of
technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the
decentralized control of fire doors, ventilation, air conditioning, etc.
Addressable applicable.


Function
4 inputs for potential-free contacts.
4 outputs with 4 potential-free relay contacts for fire control installations.
Status indication by LED.

 

8 Resistors
4 x 3k01; 1 %; 0.25 W
4 x 1k15; 1 %; 0.25 W


2 Mounting feet

Communication protocol C-NET
Operating voltage (modulated) 12... 33 VDC
Operating current (quiescent) 0.6... 0.75 mA
Relay output (ohm) 250 VAC, 4 A, max. 1000 VA
30 VDC, 4 A, max. 120 W
Connection terminals 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Humidity ≤95 % rel.
Color housing / cover white, ~RAL 9010 / transparent matt
Protection category EN60529/IEC529
– with auxiliary housing FDCH221
IP30
IP65
System compatibility C-NET FS720
Standards CEA GEI I-084, EN54-17, EN54-18
Dimensions 130 x 90 x 20 mm
Approvals VdS G204029, LPCB 126ad/02
Technical Details Table
007024
Technical Manual

 

007023
Data Sheet