FDCIO224 Input/output module

Email
Part no.: A5Q00018689
For the VdS interface for extinguishing activating devices.

Application
For the VdS interface for extinguishing activating devices.
Addressable applicable.


Function
4 inputs for potential-free contacts.
4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for the VdS interface for extinguishing
controls.
Status indication by LED.

 

 

8 Resistors
4 x 2k7; 1 %; 0.35 W
4 x 560 Ω; 1 %; 0.25 W


2 Mounting feet

Communication protocol C-NET
Operating voltage (modulated) 12... 33 VDC
Operating current (quiescent) 0.6... 0.75 mA
Relay output (ohm) 250 VAC, 4 A, max. 1000 VA
30 VDC, 4 A, max. 120 W
Connection terminals 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Humidity ≤95 % rel.
Color housing / cover white, ~RAL 9010 / transparent matt
Protection category EN60529/IEC529
– with auxiliary housing FDCH221
IP30
IP65
– with detector base seal RS720  
System compatibility C-NET FS720
Standards CEA GEI I-084, EN54-17, EN54-18
Dimensions 130 x 90 x 20 mm
Approvals VdS G207001

 

Technical Details Table
A6V10072937
Technical Manual

 

A6V10062602
Data Sheet