Application
For the VdS interface for extinguishing activating devices.
Addressable applicable.
Function
4 inputs for potential-free contacts.
4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for the VdS interface for extinguishing
controls.
Status indication by LED.
8 Resistors
4 x 2k7; 1 %; 0.35 W
4 x 560 Ω; 1 %; 0.25 W
2 Mounting feet
Communication protocol | C-NET |
Operating voltage (modulated) | 12... 33 VDC |
Operating current (quiescent) | 0.6... 0.75 mA |
Relay output (ohm) | 250 VAC, 4 A, max. 1000 VA 30 VDC, 4 A, max. 120 W |
Connection terminals | 0.2... 1.5 mm2 (2.5 mm2) |
Operating temperature | -25... +60 °C |
Storage temperature | -30... +65 °C |
Humidity | ≤95 % rel. |
Color housing / cover | white, ~RAL 9010 / transparent matt |
Protection category EN60529/IEC529 – with auxiliary housing FDCH221 |
IP30 IP65 |
– with detector base seal RS720 | |
System compatibility | C-NET FS720 |
Standards | CEA GEI I-084, EN54-17, EN54-18 |
Dimensions | 130 x 90 x 20 mm |
Approvals | VdS G207001 |