Scope of delivery
Detector and dust cap
Application
Suitable in areas in which occur different environment temperatures.
Where high dust or dirt developments or large humidity which can the impact of conventional alarm units
to impair.
Addressable applicable.
Function
Equipped with one heat sensor.
For high requirements.
Certain response behavior with slow and fast temperature increases, also by depth temperature.
Selectable detection behavior by different parameter sets.
|
Communication protocol |
C-NET |
|
Operating voltage (modulated) |
12... 33 VDC |
|
Operating current (quiescent) |
~200 μA |
|
Ext. alarm indicator |
2 |
|
Operating temperature |
-10... +50 °C |
|
Storage temperature |
-30... +70 °C |
|
Humidity |
≤95 % rel. |
|
Color |
white, ~RAL 9010 |
|
Protection category EN60529/IEC529 |
IP40 |
|
– with detector base seal RS720 |
IP42 |
|
System compatibility |
C-NET Cerberus Pro |
|
Standards |
EN54-5 / EN54-17 |
|
Dimensions |
(detector with base) Ø117 x 59 mm |
|
Approvals |
Activfire - AFP- 2468 VdS G209065 |
DB721 Detector base with loop contactFor all point detectors of the series Cerberus PRO FD720.
DBS720 Sounder baseCompatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter.
RS720 Detector base sealFor higher protection category.
FDBZ291 Designation plateTo identify the location address.
LP720 Detector Locking deviceFor locking the detector to the base.