Scope of delivery
Detector and dust cap
Application
For the detection of flaming fires caused by the combustion of liquid and solid matters, as well as smouldering fires.
For reliable fire detection in environments with deceptive phenomena.
Function
Works according to the scattered light principle with one sensor, optical forward scattering.
Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke
particles.
An additional heat sensor increases the fire detectors immunity to deceptive phenomena.
Selectable detection behaviour by different parameter sets.
Immunity against transient false alarm causes.
Built in short circuit isolator
Communication protocol |
C-NET |
Operating voltage (modulated) |
12... 33 VDC |
Operating current (quiescent) |
~230 μA |
Ext. alarm indicators that can be connected |
2 |
Permissible air speed |
max. 5 m/s |
Operating temperature |
-10... +50 °C |
Storage temperature |
-30... +70 °C |
Humidity |
≤95 % rel. |
Color |
white, ~RAL 9010 |
Protection category EN60529/IEC529 |
IP40 |
– with detector base seal RS720 |
IP42 |
System compatibility |
C-NET FS720 |
Standards |
CEA4021, EN54-7 / EN54-17 |
Dimensions |
(detector with base) Ø117 x 59 mm |
Approvals |
Activfire - AFP-2467 VdS G209064 |
For all point detectors of the series Cerberus PRO FD720.
Compatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter.
For higher protection category.
To identify the location address.
For locking the detector to the base.